Please use this identifier to cite or link to this item: http://repositoriosenaiba.fieb.org.br/handle/fieb/1798
Title: Estudo energético, exergético e ambiental de chillers de absorção movidos a fontes alternativas de energia
Other Titles: Energy, exergy and environmental study of absorption chillers powered by alternative energy sources
Authors: Santos, Ana Caroline Neves dos
metadata.dc.contributor.advisor: Santos, Alex Álisson Bandeira
metadata.dc.contributor.referees: Pessoa, Fernando Luiz Pellegrini
Keywords: Chiller por absorção;Eficiência energética;Eficiência exergética;Fontes alternativas de energia
Issue Date: 3-Aug-2023
Publisher: Centro Universitário SENAI CIMATEC
Citation: SANTOS, Ana Caroline Neves dos. Estudo energético, exergético e ambiental de chillers de absorção movidos a fontes alternativas de energia. Orientador: Alex Álisson Bandeira Santos. 2023. 84 f. Dissertação (Mestrado em Modelagem Computacional e Tecnologia Industrial) – Centro Universitário SENAI CIMATEC, Salvador, 2023.
metadata.dc.description.resumo: Diante da competição mercadológica e do estudo por novas fontes de energias alternativas, as organizações buscam por padrões de qualidade mundiais que atendam às necessidades reais da sociedade. Este trabalho tem como objetivo estudar e comparar a eficiência energética, exergética e ambiental de um sistema de pequeno porte que faz uso do chiller por absorção para conforto térmico, utilizando como fonte primária: a energia solar, biogás e gás natural. Através da 1ª lei e 2ª lei da termodinâmica foram propostos modelos termodinâmicos pode-se obter os dados a eficiência exergética e energética; a análise ambiental foi formulada a partir da metodologia do IPCC (Intergovernamental Painel on Climate Change), e as simulações propostas foram realizadas no EES® (Engineering Equation Solver). Os sistemas simulados apresentaram um COP 0,8144 e as eficiências exergéticas foram de 25,09% para o sistema solar, 15,72% para o biogás e 17,03% no gás natural. Quando comparados com as fontes alternativas com chiller por absorção a um sistema convencional (elétrico) houve cerca de 32 t CO2 evitadas.
Abstract: Faced with market competition and the study of new sources of alternative energy, organizations seek global quality standards that meet the real needs of society. This work aims to study and compare the energy, exergetic and environmental efficiency of a small system that uses the absorption chiller for thermal comfort, using as a primary source: solar energy, biogas and natural gas. Through the 1st law and 2nd law of thermodynamics, thermodynamic models were proposed to obtain data on exergy and energy efficiency. The environmental analysis was formulated based on the methodology of the IPCC (Intergovernmental Panel on Climate Change). The proposed simulations were performed in EES® (Engineering Equation Solver). The simulated systems presented a COP of 0.8144 and the exergy efficiencies were 25.09% for the solar system, 15.72% for biogas and 17.03% for natural gas. When compared to alternative sources with an absorption chiller and a conventional system, around 32 t CO2 were avoided.
URI: http://repositoriosenaiba.fieb.org.br/handle/fieb/1798
Appears in Collections:Dissertações de Mestrado (PPG MCTI)

Files in This Item:
File Description SizeFormat 
DISSERTAÇÃO_ANA CAROLINE NEVES DOS SANTOS.pdfTCCP / DISSERTAÇÃO MCTI / SENAI CIMATEC2.07 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.